Local Law 97 Compliance: 2030 Limits and the BMS Data That Proves Them

hero background
Smart Buildings and IBMS

Local Law 97 Compliance: 2030 Limits and the BMS Data That Proves Them

Back to all blogs

Short answer: Local Law 97 compliance means a covered New York City building keeps its yearly carbon emissions under a limit set by floor area and property type. From 2030 the limits drop sharply: an office falls from 0.00758 to 0.002690852 tCO2e per ft² (1 RCNY 103-14). Grid power's coefficient halves to 0.000145 tCO2e per kWh. Each tonne over can cost up to $268, so metered, auditable energy data is now a financial record.

Free Excel tool LL97 Data-Readiness Checklist and Limit Calculator comes free with this guide. Download now ↓

Applies to: New York City (US). Comparison with other US cities, the EU, UK and India in the region box below.

This post covers the 2030 limits and carbon coefficients from the official text, a worked example for a 100,000 ft² office, the BMS and meter data that proves each reporting input, deductions and good-faith rules, and a free Excel calculator and checklist.

Key takeaways

  • From 2030 the LL97 limit for an ESPM "Office" is 0.002690852 tCO2e per ft² a year, down 65% from 0.00758 in 2024 to 2029 (1 RCNY 103-14(c)(3), NYC Department of Buildings rule effective 19 January 2023).
  • Grid electricity counts as 0.000288962 tCO2e per kWh until 2029 and 0.000145 tCO2e per kWh from 2030, while natural gas stays at 0.00005311 tCO2e per kBtu (Admin Code 28-320.3.1.1; 1 RCNY 103-14(d)(3)(ii)).
  • An owner who exceeds the limit is liable for up to the excess tonnes times $268 a year (Admin Code 28-320.6, Local Law 97 of 2019; 1 RCNY 103-14(h)).
  • Owners can use an hourly time-of-use carbon coefficient only if hourly electricity is metered by the utility or sub-metered by the owner for the whole year (1 RCNY 103-14(d)(3)(iii)).
  • Urban Green Council found that 43% of covered buildings, and 47% of offices, met their 2030 limits on 2024 benchmarking data (Urban Green Council, updated January 2026).

What does local law 97 compliance require in 2030?

Local Law 97 of 2019 added Article 320 to the NYC Administrative Code. It caps the annual greenhouse gas emissions of "covered buildings", which section 28-320.1 defines as a building over 25,000 gross ft² (2,323 m²), or two or more buildings on one tax lot, or under one condo board, that together exceed 50,000 ft² (9,290 m²). Several building types are excepted, including city buildings and rent regulated accommodation.

The law runs in compliance periods. Section 28-320.3.1 covers 2024 to 2029. Section 28-320.3.2 covers 2030 to 2034. Section 28-320.3.4 asks for limits from 2035 that bring the average covered building to no more than 0.0014 tCO2e per ft² by 2050.

Every year, by 1 May, the owner files a report for the previous calendar year. A registered design professional (RDP) must certify it. It states whether the building met its limit and, if not, by how much (28-320.3.7).

The 2030 question: will calendar year 2030 emissions, filed by 1 May 2031, sit under the 2030 limit? Answering it is mostly data work.

For the deadlines and penalties of ten other US laws next to LL97, see our building performance standards tracker. This post stays in New York.

How are the LL97 2030 limits set: by occupancy group or by property type?

The statute sets limits by Building Code occupancy group. The Department of Buildings (DOB) rule sets them by Energy Star Portfolio Manager (ESPM) property type, and reporting uses the rule. Section 28-320.3.2 allows this, provided the average across covered buildings is no less strict. The statute's figures:

Occupancy group (Admin Code 28-320.3.1 and 28-320.3.2) 2024-2029 limit, tCO2e/ft² 2030-2034 limit, tCO2e/ft² Change
A (assembly) 0.01074 0.00420 -61%
B (business, other than item 6) 0.00846 0.00453 -46%
E and I-4 (education, day care) 0.00758 0.00344 -55%
I-1 (supervised residential) 0.01138 0.00598 -47%
F (factory) 0.00574 0.00167 -71%
B emergency, B lab, B ambulatory health, H, I-2, I-3 0.02381 0.01193 -50%
M (mercantile) 0.01181 0.00403 -66%
R-1 (hotels) 0.00987 0.00526 -47%
R-2 (multifamily) 0.00675 0.00407 -40%
S and U (storage, utility) 0.00426 0.00110 -74%

DOB's rule, 1 RCNY 103-14, took effect on 19 January 2023. Subdivision (c)(2) says the occupancy group of each space is set by the ESPM property type that best describes its use that year, as decided by the RDP. Subdivision (c)(3) then lists a factor for each of 60 ESPM property types for 2024 to 2029, 2030 to 2034, 2035 to 2039 and 2040 to 2049. From 2050 the factor is zero for every type.

The ESPM figures can be much tighter than the statute's. A general office is "Office" in ESPM: 0.00758 now and 0.002690852 from 2030. The statute's group B figure for 2030 is 0.00453. For 2024 and 2025 only, 103-14(c)(3)(ii) lets an owner use the occupancy-group limit where it is higher than the ESPM factor. There is no such fallback for 2030.

Bar chart of LL97 limits by ESPM property type in kgCO2e per m² a year, 2024-2029 vs 2030-2034: Office 81.6 to 29.0 (-65%), Financial Office 91.1 to 39.8, Multifamily 72.7 to 36.0, Hotel 106.2 to 41.4, Retail 81.6 to 22.7, K-12 72.7 to 24.0, Hospital 256.3 to 79.0, Data Center 256.3 to 159.2 (-38%), Non-Refrigerated Warehouse 45.9 to 9.5 (-79%)
LL97 limits by property type, 2024-2029 vs 2030-2034. Source: 1 RCNY 103-14(c)(3), NYC Department of Buildings.

In SI units, an office's limit falls from about 81.6 to 29.0 kgCO2e per m² a year. One oddity is worth knowing. The rule's 2030 factor for "Laboratory" (0.026029868) is higher than its 2024 factor (0.02381). Every other type in the table falls.

For mixed-use buildings, Equation 103-14.1 adds up each type's floor area times its factor. The floor areas must add up to the gross floor area (103-14(d)(1)).

How do the LL97 carbon coefficients change in 2030?

Your emissions are each fuel's annual use times its coefficient, summed (Equation 103-14.13). Section 28-320.3.1.1 fixes the 2024 to 2029 coefficients in the law. Section 28-320.3.2.1 left the 2030 figures to DOB, which set them in 1 RCNY 103-14(d)(3).

Energy source 2024-2029 2030-2034 Source
Grid electricity 0.000288962 tCO2e/kWh 0.000145 tCO2e/kWh 28-320.3.1.1(1); 103-14(d)(3)(ii)a
Natural gas 0.00005311 tCO2e/kBtu 0.00005311 tCO2e/kBtu 28-320.3.1.1(2); 103-14(d)(3)(ii)b
District steam 0.00004493 tCO2e/kBtu 0.0000432 tCO2e/kBtu 28-320.3.1.1(5); 103-14(d)(3)(ii)c
No. 2 fuel oil 0.00007421 tCO2e/kBtu 0.00007421 tCO2e/kBtu 28-320.3.1.1(3); 103-14(d)(3)(i)b
No. 4 fuel oil 0.00007529 tCO2e/kBtu 0.00007529 tCO2e/kBtu 28-320.3.1.1(4); 103-14(d)(3)(i)b
Bar chart of LL97 carbon coefficients in kgCO2e per MWh: grid electricity 289 in 2024-2029 and 145 from 2030 (-50%); natural gas 181 both periods; district steam 153 to 147; No. 2 oil 253 and No. 4 oil 257 unchanged
LL97 greenhouse gas coefficients by energy source. Sources: Admin Code 28-320.3.1.1 and 1 RCNY 103-14(d)(3).

A grid kWh counts half as much carbon in 2030; a kBtu of gas or oil counts the same. Buildings that burn fuel for heat lose ground. Electrified ones gain some. DOB's rule also lists coefficients for 18 other fuels, such as propane and kerosene, and its 2025 amendment added biofuel. Owners must propose a coefficient for any fuel not listed (103-14(d)(3)(i)c).

Worked example: how far over its 2030 limit is a 100,000 ft² office?

This is an illustrative example built by AOPL from the official figures. It isn't advice or a real building. Assume a 100,000 ft² (9,290 m²) office, all ESPM "Office", that uses the same energy every year: 1,800,000 kWh of grid electricity, 1,000,000 kBtu (1,000 MMBtu) of gas and 1,500,000 kBtu of district steam.

Step 1: the limit. Limit = floor area × factor. - 2024 to 2029: 100,000 × 0.00758 = 758.0 tCO2e - 2030 to 2034: 100,000 × 0.002690852 = 269.1 tCO2e

Step 2: the emissions. Emissions = Σ (energy × coefficient). - 2024: 1,800,000 × 0.000288962 + 1,000,000 × 0.00005311 + 1,500,000 × 0.00004493 = 520.1 + 53.1 + 67.4 = 640.6 tCO2e - 2030: 1,800,000 × 0.000145 + 1,000,000 × 0.00005311 + 1,500,000 × 0.0000432 = 261.0 + 53.1 + 64.8 = 378.9 tCO2e

Step 3: the gap. In 2024 the building is 117.4 t under its limit. In 2030 it's 109.8 t over, even though nothing changed inside it and the grid got cleaner.

Step 4: the exposure. Maximum penalty = 109.8 × $268 = $29,433 a year, about ₹27.7 lakh at the FBIL reference rate of ₹94.1997 per USD (1.00 pm, 13 November 2026). That repeats every year the building stays over.

Illustrative 100,000 ft² office with unchanged energy use: 2024 limit 758 t vs emissions 641 t (117 t under); 2030 limit 269 t vs emissions 379 t, 110 t over and a maximum penalty of $29,433 a year
Worked example (illustrative, not advice): the same office moves from 117 t under its limit in 2024 to 110 t over in 2030.
Line 2024-2029 2030-2034
Limit (tCO2e) 758.0 269.1
Emissions (tCO2e) 640.6 378.9
Excess (tCO2e) 0 109.8
Maximum penalty $0 $29,433 (about ₹27.7 lakh)

Electricity is still 69% of the 2030 tonnes, and steam plus gas (118 t) exceed the whole excess. So the levers are cutting electricity (controls, scheduling, lighting, fault fixes) and replacing fuel-fired heat. Both need data you can prove.

What BMS and metering data must prove each LL97 reporting input?

LL97 reports are built from utility data, not BMS screens. Your BMS or energy management system (EMS) is still where most of the evidence lives: it reconciles bills, gives the hourly and sub-metered data the rule asks for, and shows the effect of each measure. Subdivision 103-14(b)(1) says owners must keep all documentation used in the report for at least six years and hand it over on request.

Reporting input Rule What has to be proved BMS or meter data point
Floor area by ESPM type 103-14(c)(1)-(2), (d)(1) Areas match DOF records and add up to gross floor area Space register mapped to ESPM types; tenant schedule
Grid electricity, kWh 28-320.3.1.1(1) Full 12 months, every account Main incomer kWh trend, reconciled monthly to bills
Hourly electricity (TOU option) 103-14(d)(3)(iii)a-b Hourly use for every hour of the year Utility interval data, or owner sub-meter logging hourly
Gas, steam, oil 28-320.3.1.1(2)-(5) Annual kBtu by fuel Gas pulse meter, steam or condensate meter, tank level and burner run hours
Generator test fuel 103-14(d)(4)(ii) Fuel for normal testing is included Generator run hours and fuel log
EV charging (deductible) 103-14(d)(4)(ii)a One-way charging energy, separately metered Dedicated EV sub-meter
CHP, fuel cells, solar, storage 103-14(d)(3)(vi), (e)(2) Output, export and storage use Revenue-grade DER meters; inverter and net meter data
Beneficial electrification 103-14(d)(4)(iii)a Hourly, monthly and annual kWh of the heat pump or other qualifying equipment Heat pump sub-meter or equipment-integrated metering
Tenant sub-meters (LL88) Admin Code 28-311.3 Each tenant space over 5,000 ft² (465 m²) is sub-metered Tenant kWh points on the BMS or EMS
Six-year record 103-14(b)(1) Data and calculations can be produced later Historian retention of at least six years, with exports

First, the time-of-use option. Under 103-14(d)(3)(iii), an owner can replace the flat electricity coefficient with an hourly one, which can help buildings that shift load to cleaner hours or run storage. It only works if hourly consumption for the whole building is metered by the utility, or sub-metered by the owner "in a manner that produces data on such hourly consumption." If you use it for storage or DER, you must use it for all utility electricity. A BMS with gaps in its kWh trend can't support that claim.

Second, beneficial electrification. DOB's rule effective 20 January 2024 gives qualifying electric equipment a negative coefficient: -0.0013 tCO2e per kWh for equipment installed and running before 1 January 2027, and -0.00065 for equipment installed from 2027 to 2029 (103-14(d)(3)(vii)). The metered route needs hourly, monthly and annual records for that equipment, kept six years. Savings can be banked and used in a later year up to 2036, on a sliding schedule. Equipment under 1,200,000 Btu/h of rated heating capacity can use a deemed calculation instead; the rule gives formulas for air-source heat pumps and heat pump water heaters (103-14(d)(4)(iii)b).

For what to sub-meter and why, see our guide to smart energy meters and sub-metering. Our building energy management system guide covers the controls and fault detection that cut the electricity line.

Which deductions and adjustments can lower an LL97 number?

Deductions reduce reported emissions. Adjustments change the limit itself. Both need paperwork.

  • Renewable energy credits (RECs). Section 28-320.3.6.1 allows a deduction for RECs from a resource that is a capacity resource in, or directly deliverable to, NYISO Zone J, from the same year, retired by or for the owner. Rule 103-14(e)(1) limits RECs to emissions from utility electricity.
  • Offsets. Section 28-320.3.6.2 allows offsets up to 10% of the limit for 2024 to 2029. DOB's rule effective 19 January 2025 recognises only offsets from the city's Affordable Housing Reinvestment Fund (AHRF), still capped at 10% of the limit, and makes them available in each compliance period (103-14(e)(3)).
  • Solar and storage. For 2024 to 2029, exported on-site solar can be deducted, and on-site storage earns a deduction of rated capacity × emissions spread × 85% efficiency (103-14(e)(2), Equation 103-14.17).
  • Adjustments. Section 28-320.7 allows an adjustment where capital improvements can't reasonably be made or where financial hardship applies. Section 28-320.8 covered 2024 to 2029 for buildings whose 2018 emissions were more than 40% over the 2024 limit because of special uses, such as 24-hour operations. Section 28-320.9 covers not-for-profit hospitals and health centres. As enacted, the law set 2021 application deadlines for the last two (28-320.8.2 and 28-320.9). Applications under 28-320.7 and 28-320.8 must be certified by an RDP.

What counts as good faith efforts, and why does LL88 matter?

Section 28-320.6.1 tells the tribunal to weigh good-faith efforts, compliance history, unforeseeable events and access to money when it sets the penalty. DOB's rule effective 20 January 2024 defines good faith for 2024 to 2029 in 103-14(i)(2). It's demanding. The owner must file the LL97 report, upload LL84 benchmarking, and attest that LL88 lighting upgrades and tenant sub-meters are done. Then they need at least one of these:

  • a decarbonisation plan certified by an RDP and filed by 1 May 2025, with an energy audit no older than four years, a full HVAC and hot water inventory, and a capital plan (no REC deductions for 2024 to 2029 on this path);
  • an approved DOB application, or a signed contract and proof of payment, for the work that brings the building into compliance;
  • approved electrical work and a utility load letter for electrification;
  • an earlier report showing the building was under its limit;
  • critical-facility status, or an adjustment applied for or granted.

DOB says plainly that good faith for 2030 to 2034 will be defined differently, and that owners now in compliance should already be planning for 2030.

LL88 is the part facility teams forget. Local Law 134 of 2016 required lighting in buildings over 25,000 ft² to meet current energy code standards by 1 January 2025 (Admin Code 28-310.3). Local Law 132 of 2016 required sub-meters in every tenant space over 5,000 ft² by the same date (28-311.3). Without both, an owner can't claim good faith. The sub-meters also give you the tenant-level data to find savings.

What penalties apply if a building misses its limit or the report?

The headline is up to $268 per excess tonne a year (28-320.6, set at that maximum by 103-14(h)). At ₹94.1997 per USD that's about ₹25,245 a tonne. Missing the report costs up to $0.50 per ft² of gross floor area for each month it isn't filed within 12 months of the deadline, after 60 days' grace (28-320.6.2; 103-14(g)). A knowingly false statement is a misdemeanour with fines of up to $500,000 (28-320.6.3), which is one more reason to keep a clean data trail.

Regulation by region: how does LL97 compare?

Region Rule What it asks of existing buildings
Other US cities and states Building performance standards in Boston, Washington State, Colorado, Maryland and others See our BPS tracker for limits, filing dates and penalties
EU Directive (EU) 2024/1275 (EPBD recast) Member states set minimum energy performance standards so non-residential buildings are below the worst-16% threshold from 2030 and the worst-26% threshold from 2033, checked by energy performance certificate
UK (England and Wales) MEES, government interim response of 18 June 2026 Proposed: private rented buildings over 1,000 m² to reach EPC B from 2031 where cost-effective
India ECSBC 2024 (Bureau of Energy Efficiency) A design code for commercial buildings with 100 kW connected load or 120 kVA contract demand and above; no annual operating carbon cap

LL97 differs from the EU and UK rules in one way that matters for data. It's an operating cap measured every year from metered energy, not a certificate rating. Our EPBD Article 13 guide covers Europe's building automation rules, and the EPBD transposition tracker shows where each country stands. India's ECSBC 2024 works at design stage.

If you run New York buildings from India

Indian groups and global capability centres that own, lease or manage NYC space face the same filing. The filing is the owner's duty, so leases should say who gives access to meter and sub-meter data. Remote monitoring from India works if the BMS or EMS keeps clean hourly data and a six-year archive.

Questions to ask your RDP or BMS vendor before 2030

  1. Which ESPM property type will you assign to each space, and what is our 2030 limit in tonnes?
  2. What is our forecast 2030 emissions figure, using the 0.000145 kWh coefficient and our current fuel use?
  3. Does our main electricity meter, or the utility, give us hourly data for every hour of the year?
  4. Are all DER, EV chargers and new heat pumps sub-metered in a way that produces auditable data for the reporting year?
  5. Do our LL88 lighting and tenant sub-meter filings exist, and can we find them?
  6. How long does our BMS historian keep trend data, and can it export it in an open format?
  7. Which measures close our 2030 gap, in what order, and what does each save in tonnes?
  8. If we electrify heat before 2027, how do we bank the beneficial electrification credit?

Free download: LL97 Data-Readiness Checklist and Limit Calculator

Preview of the free LL97 limit calculator in Excel
Free Excel tool
LL97 Data-Readiness Checklist and Limit Calculator
Enter floor area by property type and a year of electricity, gas, steam and oil. The sheet applies the official LL97 factors and coefficients and shows your 2024-2029 and 2030-2034 limits, emissions, excess tonnes and maximum penalty in USD and ₹.
  • All 60 ESPM property-type factors from 1 RCNY 103-14
  • 2024 and 2030 limits, excess tonnes and penalty at $268 per tonne
  • 22-item checklist mapping each data item to its rule and evidence source
Download the free Excel file ↓
Excel (.xlsx) · Example office filled in · No sign-up

The calculator applies all 60 ESPM factors and both sets of coefficients to your floor areas and energy use, and shows limits, emissions, excess tonnes and maximum penalty in USD and ₹ for 2024 to 2029 and 2030 to 2034. The checklist sheet lists 22 data items, each with its rule clause and the BMS, meter or document that proves it.

FAQs

What is the LL97 2030 limit for an office building? For a space classified as ESPM "Office", 0.002690852 tCO2e per ft² a year, or about 29 kgCO2e per m² (1 RCNY 103-14(c)(3)(iii)). Multiply by the office floor area to get the limit in tonnes.

Does the 2030 grid coefficient make compliance easier? For electricity, yes: it halves from 0.000288962 to 0.000145 tCO2e per kWh. Gas and oil coefficients don't change, while the limits fall by 38% to 79% for common types, so fuel-heated buildings often move from compliant to over.

Can BMS data replace utility bills in an LL97 report? No. Bills and utility data remain the core record. BMS and sub-meter data support the hourly time-of-use option, deductions, beneficial electrification and the six-year evidence trail.

When is the first report under the 2030 limits due? Reports are due by 1 May each year for the previous calendar year (Admin Code 28-320.3.7), so calendar year 2030 is reported by 1 May 2031.

Can RECs or offsets close the whole gap? RECs only offset utility electricity emissions and must meet Zone J and same-year conditions. AHRF offsets are capped at 10% of the limit. Owners on the decarbonisation-plan route can't use RECs for 2024 to 2029.

Asset Online Pvt Ltd (AOPL) supplies and integrates solutions in this area, including BMS, energy metering and sub-metering. To check whether your building data can prove LL97 compliance, talk to our smart buildings team or see our smart building solutions.