Short answer: a smart lighting system lets you switch, dim and schedule each light or group from software, and use sensors for occupancy and daylight. DALI is a lighting-only protocol: two wires carry power and data to up to 64 drivers per line. KNX is a whole-building bus that handles lighting along with blinds, HVAC and more. Wireless options suit retrofits where new cabling is hard. Controls can cut lighting energy by 24 to 38% on average, and ECSBC 2024 now requires many of them.

This guide compares DALI, KNX and wireless, sets out what the code requires, shows where the savings come from, and lists what to ask before you buy.

What makes a lighting system "smart"?

Three things separate it from a switch on the wall:

  • Addressability. Each light or driver has an address, so software can control it alone or in any group, without rewiring.
  • Inputs. Occupancy sensors, daylight sensors, schedules and wall keypads tell the system what to do.
  • Feedback. The system reports lamp failures, energy use and status back to the building management system.

The protocol you pick decides how far you can take each of these.

How does DALI work?

DALI (Digital Addressable Lighting Interface) is a dedicated protocol for digital lighting control, defined in the international standard IEC 62386 (DALI Alliance). Each device has its own address and can also be placed in groups, so you can change zones in software without changing wires.

Diagram of a DALI subnet: bus power supply, application controller and input devices on a two-wire bus with up to 64 control gear and 64 control devices, maximum 300 m
What one DALI subnet can hold. Source: DALI Alliance.

The DALI Alliance sets out the system limits (DALI Alliance, DALI systems):

  • Power and data share the same two wires, typically standard 2-core 1.5 mm² cable. Polarity doesn't matter and free topology is allowed.
  • Each subnet takes up to 64 control gear (LED drivers) and 64 control devices (controllers, sensors, switches).
  • Maximum cable length between the furthest devices is 300 m.
  • A bus power supply gives typically 16 V and up to 250 mA.

DALI-2 is the current certification programme, with much wider testing than version 1 and a focus on interoperability. Check that drivers, sensors and controllers are DALI-2 certified, not just "DALI compatible".

D4i extends DALI into the luminaire. D4i drivers can report energy use, diagnostics and maintenance data, which helps with asset management and predictive maintenance (DALI Alliance, D4i). If you want to know which fittings are failing before tenants complain, ask for D4i.

How does KNX compare?

KNX is an open building automation standard, not a lighting-only protocol. The KNX Association says it has been in use for over 30 years, with more than 8,000 certified devices from over 500 manufacturers, all configured through one software tool, ETS (KNX Association).

Point DALI KNX Wireless (Zigbee, Bluetooth mesh and similar)
Scope Lighting only Lighting, blinds, HVAC, sensors, metering Mostly lighting and sensors
Wiring 2-wire bus to each driver Bus cable to actuators and devices No control wiring
Typical use Offices, factories, retail with many fittings Premium offices, hotels, homes where one system runs the room Retrofits, heritage buildings, small sites
Dimming at fitting Native (DALI driver) Usually through a DALI gateway or dimming actuator Native in wireless driver or node
Interoperability DALI-2 certification KNX certification Varies by ecosystem; check carefully
BMS link Gateway to BACnet or IP Gateway to BACnet or IP Gateway; check data available

In practice, many large projects use both: DALI to the fittings and KNX or BACnet above it. The DALI Alliance also publishes specifications for wireless-to-DALI gateways, so a wireless sensor or switch can talk to a wired DALI system.

What does ECSBC 2024 require for lighting control?

The Energy Conservation and Sustainable Building Code 2024 from the Bureau of Energy Efficiency sets these mandatory lighting controls (BEE, ECSBC 2024):

  • Automatic shutoff (7.2.2a). At least 90% of interior lighting by wattage must be on automatic control, by schedule or occupancy sensor. Occupancy sensors must switch off or dim by at least 80% within 15 minutes of a space emptying.
  • Space control (7.2.2b). Each enclosed space needs its own control. Offices over 30 m² must limit general lighting control zones to 60 m².
  • Daylight areas (7.2.2c). Luminaires within the daylit zone near windows need either a manual control or an automatic control with at least a 5-minute delay that can switch off or dim to 10% of full power. If automatic, manual override isn't allowed.
  • Exterior lighting (7.2.3). Controlled by a photo sensor or astronomical time clock. Facade lighting and non-emergency signage need separate time control.

For ECSBC Plus and Super ECSBC buildings (7.2.4), a centralised lighting control system is mandatory, with switching, dimming and scheduling of individual or grouped luminaires, occupancy feedback, luminaire failure feedback and separate energy monitoring for internal and external lighting. That list reads like a DALI-2 or D4i specification. Our ECSBC 2024 guide explains which buildings are covered.

How much energy do lighting controls save?

Lawrence Berkeley National Laboratory pooled 240 savings estimates from 88 studies of commercial buildings (Williams et al., LBNL-5095E). Average savings of lighting energy were:

Strategy Average saving
Occupancy sensors 24%
Daylight harvesting 28%
Personal tuning (users set their own levels) 31%
Institutional tuning (set levels to what the task needs) 36%
Multiple strategies combined 38%

The study found that simulations overestimate daylighting savings by at least 10% compared with real buildings. Ask vendors for measured results, not just models.

India has seen what controlled LED lighting can do at scale. By January 2025, EESL had installed over 1.34 crore LED streetlights under the Street Lighting National Programme, saving over 9,001 million units of electricity a year and cutting peak demand by more than 1,500 MW (PIB, Ministry of Power, 6 January 2025). Those savings came mostly from the switch to LED. Controls are the next step once fittings are efficient.

Which should you choose?

  • New office or factory with many fittings: DALI-2 to the drivers, D4i if you want fitting-level data, gateway to the BMS. See our lighting and daylight products.
  • Hotel, premium office or home where lighting, blinds and HVAC run together: KNX for room control, DALI for dimming where needed.
  • Retrofit where you can't pull new cable: wireless nodes or wireless-to-DALI gateways. Test coverage and latency before a full roll-out.
  • Large campus: whichever you pick at room level, insist on an open link to the BMS (BACnet/IP is common). Our BACnet guide explains why.

Questions to ask a lighting control vendor

  1. Are the drivers, sensors and controllers DALI-2 certified? Show the product database entries.
  2. Do the luminaires support D4i energy and diagnostic reporting?
  3. How many DALI subnets will the floor need, and where are the gateways?
  4. How does the system meet ECSBC 7.2.2 timings: 15-minute shutoff, 80% dimming, daylight zone controls?
  5. Which BMS protocol does the gateway expose, and which points are available?
  6. Can our team change zones and schedules ourselves, or does every change need your engineer?
  7. Can you show measured savings from a similar Indian building?

FAQs

What is the difference between DALI and KNX? DALI is a lighting-only protocol that addresses each driver over two wires. KNX is a building automation bus that covers lighting, blinds, HVAC and more. Many projects use DALI for fittings and KNX or BACnet above it.

How many devices can one DALI line control? Up to 64 control gear and 64 control devices per subnet, with a maximum cable length of 300 m.

What is DALI-2? The current DALI certification programme from the DALI Alliance, with more thorough testing for interoperability than version 1.

How much can smart lighting save? Average lighting savings range from 24% for occupancy sensors to 38% for combined strategies, according to an LBNL meta-analysis of 240 estimates.

Is smart lighting control mandatory in India? For buildings covered by ECSBC 2024, automatic controls on at least 90% of interior lighting are mandatory, and ECSBC Plus and Super ECSBC buildings need a centralised lighting control system.

Planning lighting controls for a new building or retrofit? Talk to our smart buildings team or see our smart building solutions.

Sources

  • DALI Alliance, What is DALI: dali-alliance.org
  • DALI Alliance, DALI systems and components: dali-alliance.org
  • DALI Alliance, D4i overview: dali-alliance.org
  • KNX Association, What is KNX: knx.org
  • Bureau of Energy Efficiency, ECSBC 2024, section 7.2: beeindia.gov.in
  • Williams et al., Meta-Analysis of Energy Savings from Lighting Controls, LBNL-5095E: LBNL
  • PIB, UJALA and SLNP: 10 years of energy-efficient lighting, 6 Jan 2025: pib.gov.in