Short answer: an occupancy sensor detects whether a space is in use and switches or dims lights, and can set back air conditioning, when it isn't. A US national lab meta-analysis puts average lighting savings from occupancy sensors at 24%. The bigger prize is HVAC: a US Department of Energy study found people-counting sensors that adjust airflow saved 17.8% of whole-building energy, against 5.9% for simple presence sensors. India's ECSBC 2024 already requires occupancy controls in many spaces.
This guide covers sensor types, what the code requires, where the savings come from, privacy, and what to ask a vendor.
What does an occupancy sensor actually do?
It answers one of two questions:
- Is anyone here? Presence or vacancy sensing. Used to switch or dim lights and put a room's air conditioning into standby.
- How many people are here? People counting. Used to set fresh air, cooling and cleaning to match real use, and to plan space.
The first is cheap and common. The second costs more but drives much larger HVAC savings, because ventilation and cooling are sized for full occupancy that rarely happens.
Which occupancy sensor types are there?
| Sensor | How it detects | Good for | Watch out for |
|---|---|---|---|
| PIR (passive infrared) | Changes in body heat moving across zones | Cabins, corridors, toilets | Misses people sitting still; needs line of sight |
| Ultrasonic | Doppler shift of sound waves | Partitioned rooms, toilets with stalls | False triggers from air flow or vibration |
| Dual technology (PIR + ultrasonic) | Both must agree to switch on; either holds | Offices and meeting rooms | Costs more; needs proper set-up |
| Microwave radar | Reflected radio waves, including small movements | Open areas, high ceilings | Can see through thin partitions |
| Thermopile or time-of-flight | Heat pixels or depth image | Desk and room counting without video | Coverage per sensor is limited |
| Camera with AI counting | Video analysed for people | Entrances, large halls, cafeterias | Privacy; must handle personal data lawfully |
For lighting, dual technology sensors are the safe default in offices. For people counting, thermopile and time-of-flight sensors give counts without capturing faces. See our occupancy and people counting products.
What does ECSBC 2024 require?
The Bureau of Energy Efficiency's Energy Conservation and Sustainable Building Code 2024 makes occupancy control mandatory in several places (BEE, ECSBC 2024). Our ECSBC 2024 guide covers who must comply.
Lighting (section 7.2.2):
- At least 90% of interior lighting by wattage must have automatic control, either on a schedule or by occupancy sensors.
- Occupancy sensors must switch off or dim lights by at least 80% within 15 minutes of a space becoming empty, with a wall switch for manual control.
- Occupancy sensors are required in enclosed habitable spaces under 30 m², storage or utility spaces over 15 m², public toilets over 25 m², corridors of hospitality buildings, and all conference or meeting rooms.
- Exceptions include lighting needed 24/7, patient care areas, and places where automatic shutoff would endanger safety or security.
HVAC (section 6.2.3):
- Occupancy controls must be installed at zone level to shut down, or cut to a minimum, fresh air and air conditioning when a zone is empty. The code gives hotel rooms, office cabins, conference rooms, classrooms and hospital rooms as examples.
- If equipment can't be turned off, the set-point must rise automatically to 27°C or higher.
Ventilation (section 6.2.1): systems that supply more than 5,400 m³/h of outdoor air to air-conditioned space need demand-controlled ventilation, for example dampers driven by CO2 sensors at breathing height in spaces over 50 m². CO2 here works as a proxy for how many people are in the room. ASHRAE's June 2026 brief supports CO2 for demand-controlled ventilation, but warns that a CO2 reading on its own is not a measure of indoor air quality (ASHRAE, Indoor CO2, ventilation and IAQ).
Super ECSBC buildings go further. Air conditioning serving large zones such as workstation areas must be able to save energy based on real-time headcount. That's a people-counting requirement, not just presence.
How much energy do occupancy sensors save?
Start with lighting. Lawrence Berkeley National Laboratory pooled 240 savings estimates from 88 studies (Williams et al., LBNL-5095E).
Occupancy sensors averaged 24% of lighting energy. Combining strategies averaged 38%. The same study found simulations overstate daylighting savings by at least 10%, a useful warning when a vendor shows modelled numbers.
Lighting is a modest share of a modern office's energy, especially after an LED retrofit. HVAC is where occupancy data pays most. Pacific Northwest National Laboratory simulated a large office with VAV air conditioning across all 15 US climate zones (PNNL-22072, US DOE, 2013):
Three points stand out:
- Lighting-only occupancy control saved less than 1.1% of total building energy in every climate.
- Adding presence-based control of VAV boxes raised the US average to 5.9%.
- Counting people and resetting minimum airflow to match raised it to 17.8%, about three times as much in most climates.
PNNL explains why. Installers often set minimum airflow at 30 to 50% of the box maximum, sized for a full room, and leave it there. Meeting rooms and cafeterias sit empty much of the day, so fans move and cool air nobody needs.
Climate matters. Whole-building savings were smallest in hot, humid Miami, which is the nearest US match to coastal Indian cities. Indian results will depend on climate, HVAC type and how much of the day spaces sit empty. Treat the US numbers as direction, not a promise, and measure your own baseline.
Where should you start in an existing building?
- Meeting rooms and training rooms. Often empty, often fully cooled. Sensors plus an HVAC set-back pay back fastest.
- Cabins and small offices. Required by ECSBC under 30 m², and easy to retrofit.
- Toilets, stores and utility rooms. Low cost, quick wins on lighting.
- Open-plan floors. Use people counting to set ventilation and to see real desk use before you lease more space.
- Cafeterias and auditoriums. Big air volumes, very uneven use. Counting at entrances plus CO2-based ventilation.
Connect sensors to the building management system rather than running stand-alone switches. That way the same data controls lights, air conditioning and ventilation, and reports utilisation. Our BACnet guide explains how sensors talk to a BMS.
What about privacy with camera-based counting?
Counting sensors that don't capture images avoid most privacy questions. If you use cameras, the video can identify people, and India's Digital Personal Data Protection Act applies. Process counts on the device where possible, keep only totals, set short retention for any video, and put up notices. Our face recognition and DPDP guide covers the rules.
Questions to ask an occupancy sensor vendor
- Which detection technology is this, and what is its coverage pattern at our ceiling height?
- What is the counting accuracy at entrances and in open areas, and how was it tested?
- Does the sensor talk BACnet, Modbus or another open protocol to our BMS?
- Can the time delay and dimming level be set to meet ECSBC (off or 80% dim within 15 minutes)?
- Does any image leave the device? If yes, where is it stored and for how long?
- What is the battery life, if wireless, and how are failures reported?
- Can you show measured savings from a similar Indian building, not just a simulation?
FAQs
What is an occupancy sensor? A device that detects whether people are in a space and controls lights, air conditioning or ventilation to match.
How much energy does an occupancy sensor save? LBNL's meta-analysis found 24% of lighting energy on average. When sensors also control air conditioning airflow, a DOE study found whole-building savings of 5.9% with presence sensors and 17.8% with people counting.
Is an occupancy sensor mandatory in India? Under ECSBC 2024, yes in many spaces, including enclosed rooms under 30 m², meeting rooms and larger toilets and stores, where the code applies to your building.
PIR or ultrasonic: which is better? PIR is cheaper and suits open sight lines. Ultrasonic catches small movements behind partitions. Dual technology combines both and cuts false switching.
Can occupancy sensors control air conditioning? Yes. ECSBC requires zone-level controls to cut air conditioning and fresh air in empty zones, or raise the set-point to 27°C or more.
Planning occupancy-based controls for an office, hotel or campus? Talk to our smart buildings team or see our smart building solutions.
Sources
- Bureau of Energy Efficiency, Energy Conservation and Sustainable Building Code 2024, sections 6.2.1, 6.2.3, 7.2.2: beeindia.gov.in
- Williams, Atkinson, Garbesi, Rubinstein and Page, A Meta-Analysis of Energy Savings from Lighting Controls in Commercial Buildings, LBNL-5095E: LBNL
- ASHRAE, Indoor carbon dioxide, ventilation and indoor air quality, updated Jun 2026: ASHRAE
- Zhang, Liu, Lutes and Brambley, Energy Savings for Occupancy-Based Control of VAV Systems, PNNL-22072, Jan 2013: PNNL