Short answer: IT/OT convergence is safe only when the plant network is split into layers that can't talk to each other freely. The Purdue model gives the layers: field devices, controllers, HMI and SCADA, site operations, then business IT, with a DMZ between plant and office. ISA/IEC 62443 turns that into zones and conduits with defined security levels. NIST's OT guide says to allow traffic only between adjacent levels, so office systems never reach PLCs directly.
This guide covers the Purdue levels, IEC 62443 zones and conduits, how to design the DMZ and remote access, India's reporting rules, a phased plan and vendor questions.
Why does IT/OT convergence raise the risk?
Plants want data out of the shop floor: OEE dashboards, MES, predictive maintenance, energy reports. That means connecting networks that used to be isolated.
NIST's Guide to Operational Technology Security explains the problem. OT systems were once isolated and ran proprietary protocols. As they adopted standard computers, operating systems and network protocols for business connectivity and remote access, they started to resemble IT systems and lost much of their isolation (NIST SP 800-82r3, September 2023).
NIST also notes that many field devices and protocols at Level 0, such as sensors and actuators, can't be authenticated. Data from them can be replayed, changed or spoofed. You can't patch your way out of that; you have to control who can reach them.
What is the Purdue model?
The Purdue model groups plant systems into levels. NIST's guide shows it with a DMZ between the plant and business networks:
| Level | Name in NIST's figure | Typical systems |
|---|---|---|
| 5 | Enterprise | Email, ERP, internet access |
| 4 | Business planning and logistics | Plant IT, scheduling, MES links |
| DMZ | Demilitarised zone | Historian copy, patch and antivirus servers, remote access jump host |
| 3 | Operations and control | Site historian, engineering workstations |
| 2 | Area control (HMI) | SCADA servers, HMIs |
| 1 | Controller network | PLCs, DCS controllers |
| 0 | Field I/O devices | Sensors, drives, actuators |
The "typical systems" column is our illustration; the level names come from NIST.
The key rule from NIST: permit connections only between adjacent levels. A Level 4 device should never talk directly to Level 2, 1 or 0. NIST also says outbound rules from the control network should be as strict as inbound rules, and that unidirectional gateways (data diodes) are an alternative to firewalls where data only needs to flow one way.
How do IEC 62443 zones and conduits fit in?
ISA/IEC 62443 is a series of cybersecurity standards for industrial automation and control systems. ISA describes it as covering requirements and processes for implementing and maintaining these systems, across sectors from process plants to building automation and power (ISA, ISA/IEC 62443 series).
The series has four groups of documents:
| Group | Parts | Who uses it |
|---|---|---|
| General | 1-x: terms, concepts, models | Everyone |
| Policies and procedures | 2-1 security programme, 2-3 patch management, 2-4 service providers | Asset owners, service providers |
| System | 3-2 risk assessment, 3-3 system requirements and security levels | Asset owners, integrators |
| Component | 4-1 secure development, 4-2 component requirements | Product suppliers |
Where Purdue thinks in levels, 62443 thinks in zones (groups of assets with the same security needs) and conduits (the controlled paths between them). NIST's figure shows a 62443 layout with separate zones for the enterprise, the DMZ, the control centre, the basic process control system and the safety instrumented system (SIS), each joined by conduits. Keeping the SIS in its own zone is the point: a problem in the process network shouldn't reach the system that shuts the plant down safely.
ISA also stresses shared responsibility between asset owners, integrators, product suppliers and service providers. In contracts, that means naming who does what.
What does a good plant DMZ look like?
The DMZ is where IT and OT meet without touching. A practical design:
- Historian replication. The plant historian at Level 3 pushes data to a copy in the DMZ. Business users read the copy, never the original.
- Patch and antivirus staging. Updates are downloaded to a DMZ server, checked, then pushed to Level 3. OT machines don't browse the internet.
- Remote access jump host. Vendors and engineers connect to a hardened jump host in the DMZ with MFA, then reach specific OT assets through logged sessions.
- Two firewalls or one with strict zones. One between IT and DMZ, one between DMZ and OT, with no rule that lets traffic pass straight through.
- Data diodes for one-way flows. Where OT only needs to send data out, a unidirectional gateway removes the inbound path completely.
Our IoT gateway guide covers protocol conversion at the edge, and edge computing for Indian factories covers where analytics should run.
What should you do first?
CISA and partner agencies published five primary mitigations for OT on 6 May 2025 (CISA, Primary Mitigations to Reduce Cyber Threats to OT):
- Remove OT connections to the public internet. Internet-facing OT devices are easy to find and often lack strong authentication.
- Change default passwords and use strong, unique ones.
- Secure remote access. Use a private connection and a VPN with phishing-resistant MFA, least privilege, and disable dormant accounts.
- Segment IT and OT networks, using a DMZ to pass control data to business systems.
- Practise manual operation. Test continuity plans, fail-safes, backups and standby systems so the plant can run safely during an incident.
These cost little compared with a full redesign. CISA notes that targeted systems often had default or easily guessed passwords.
What do Indian rules require?
CERT-In's directions of 28 April 2022 apply to service providers, intermediaries, data centres, body corporates and government organisations (CERT-In Directions under section 70B, 28 April 2022). For plants, three points matter:
- Report within 6 hours. The list of reportable incidents in Annexure I includes attacks on critical infrastructure, SCADA and operational technology systems, and attacks on IoT devices.
- Keep logs for 180 days. Logs of all ICT systems must be kept securely for a rolling 180 days within India.
- Sync clocks. Systems must connect to NTP servers of NIC or NPL, or servers traceable to them.
In practice, OT logging is often the gap. Some PLCs and HMIs have limited logging, so put logging and time sync on the firewalls, jump hosts and historian at the zone boundaries. Our CERT-In and DPDP guide covers the wider rules.
How should you phase an IT/OT segmentation project?
| Phase | What you do | Output |
|---|---|---|
| 1. Discover | Inventory every OT asset, its level, IP address and the flows it needs | Asset list and data-flow map |
| 2. Quick wins | Internet exposure check, default passwords, remote access clean-up | CISA's five steps done |
| 3. Design | Define zones and conduits, the DMZ, firewall rules, logging | Zone diagram and rule set |
| 4. Build in windows | Change one cell or line at a time during planned shutdowns | Segmented network, tested |
| 5. Monitor | OT-aware monitoring at conduits, log review, incident drills | Alerts, 180-day logs, drill reports |
NIST says grouping assets into levels, tiers or zones is the step that comes before any isolation devices. Skip discovery and you risk blocking a data flow that production depends on.
Questions to ask an OT network or security vendor
- How will you build the asset inventory without disrupting production?
- Which reference model will you use, Purdue, IEC 62443 zones, or both, and why?
- What will sit in the DMZ, and how will historian data reach business users?
- How will vendor remote access work: MFA, session recording, approval per session?
- How will you keep logs for 180 days and sync time for CERT-In compliance?
- Is the SIS in its own zone, and who signs off changes to it?
- Which changes need a shutdown, and how will you test rollback?
- Do the products you supply have IEC 62443-4-2 certification, and does your team follow 62443-2-4?
FAQs
What is the Purdue model in OT security? A reference model that groups plant systems into levels, from field devices (Level 0) to enterprise IT (Level 5), with a DMZ between plant and business networks.
What is the difference between Purdue and IEC 62443? Purdue gives the levels. IEC 62443 groups assets into zones with defined security levels and controls the conduits between them. Many plants use both.
Do Indian plants have to report OT cyber incidents? CERT-In's 2022 directions list attacks on SCADA and operational technology systems among incidents to report within 6 hours.
Is an air gap still a good idea? Where a system needs no outside data, yes. Where data must flow out, a DMZ or a data diode gives control without full isolation.
Should OT devices be on the internet? No. CISA's first mitigation is to remove OT connections to the public internet.
Planning IT/OT segmentation for a plant? See our network security and cybersecurity solutions or contact us.
Sources
- NIST SP 800-82r3, Guide to Operational Technology (OT) Security, September 2023: PDF
- ISA, ISA/IEC 62443 Series of Standards: page
- CISA, Primary Mitigations to Reduce Cyber Threats to Operational Technology, 6 May 2025: page
- CERT-In, Directions under sub-section (6) of section 70B of the IT Act, 2000, 28 April 2022: PDF