Short answer: an IoT gateway is the box that sits between plant equipment and your IT or cloud systems. It reads machines over field protocols such as Modbus and OPC UA, converts and buffers the data, and sends it on, often over MQTT with TLS encryption. A good gateway also acts as a security boundary. In India, IoT gateways come under the Telecommunication Engineering Centre's essential requirements, revised on 19 June 2026. Size the gateway by device count, polling rate, local storage and edge apps, not just ports.
This guide covers what a gateway does, the main protocols, how to harden it, how to size it, the Indian rules, and what to ask a supplier.
What does an IoT gateway do?
Five jobs, in order of how often they cause trouble:
- Talk to field devices. Poll PLCs, meters, drives and sensors in their own protocol.
- Convert and tag data. Turn register 40001 into "Compressor 2 discharge pressure, bar" with a time stamp.
- Buffer. Store data locally when the network or cloud link drops, then send it when the link returns.
- Run edge logic. Filter, average, raise alarms or run small analytics close to the machine.
- Protect the plant. Act as the only defined route between the control network and the outside.
Gateways are different from edge servers. A gateway handles connectivity and light processing. An edge server runs heavier workloads such as machine vision or a local historian. Many sites use both. Our edge computing guide covers that layer.
Which protocols should a gateway support?
| Protocol | Where you'll meet it | Notes |
|---|---|---|
| Modbus RTU (RS-485) | Energy meters, drives, older instruments | Simple and everywhere; no built-in security; slow serial links limit how many devices you can poll quickly |
| Modbus TCP | PLCs, newer meters | Same data model over Ethernet; still no built-in security |
| OPC UA | Modern PLCs, SCADA, MES | Platform-independent; built-in security with X.509 certificates, encryption, signing and audit |
| MQTT | Gateway to cloud or data platform | Lightweight publish-subscribe; three delivery levels |
| BACnet | Building management systems | See our BACnet guide |
| Vendor protocols | Specific PLC brands, legacy kit | Check driver availability before you buy |
OPC UA was released in 2008 to bring the older OPC specifications into one framework. The OPC Foundation lists its security features: each client and server is identified by X.509 certificates, messages can be encrypted and signed, packets are sequenced against replay attacks, and user activity can be audited (OPC Foundation, OPC UA).
MQTT 5.0 became an OASIS Standard on 7 March 2019. It's a client-server publish-subscribe protocol built for small code footprints and limited bandwidth (OASIS, MQTT 5.0). It offers three quality-of-service levels:
- QoS 0, at most once. Fine for frequent sensor readings where one lost value doesn't matter.
- QoS 1, at least once. Delivery assured, duplicates possible. Your platform must handle repeats.
- QoS 2, exactly once. Use where a duplicate or a loss would cause a real error, such as billing or batch counts.
The standard says implementations should offer authentication, authorisation and secure communication. In practice that means TLS, unique credentials per device and topic-level access control on the broker.
How do you secure an IoT gateway?
The ISA/IEC 62443 series is the main standard for industrial control system security. It covers building automation, power, process and other sectors, and stresses shared responsibility between asset owners, suppliers, integrators and service providers. ISA/IEC 62443-4-2 sets technical security requirements for components such as gateways. ISA/IEC 62443-3-3 sets system requirements and security levels (ISA, ISA/IEC 62443 series).
A practical hardening checklist:
- Change every default password and disable unused accounts.
- Close unused ports and services. No open web admin page on the plant network unless you need it.
- Make connections outbound only. The gateway publishes to the broker; nothing on the internet should connect inbound.
- Use TLS and certificates for MQTT and OPC UA. Keep a list of certificate expiry dates.
- Separate networks. Put the gateway between the OT and IT networks with a firewall, not on a flat network.
- Patch on a schedule. Ask the supplier how often firmware is updated and how you're told.
- Log and forward. Send gateway logs to your security monitoring.
Indian companies also have incident reporting duties under CERT-In directions. Our cyber security guide for mid-size companies covers them.
What Indian rules apply to IoT gateways?
IoT gateways have their own Telecommunication Engineering Centre (TEC) standards in India. Two recent notifications matter:
- Revised Essential Requirements, 19 June 2026. The Department of Telecommunications notified revised TEC Essential Requirements for five device types, including IoT gateways (TEC 24492607), smart electricity meters, tracking devices and end-point devices for environmental monitoring. Old and revised standards run together for 90 days, after which only the revised versions apply (Gazette of India, S.O. 3349(E)).
- Generic Requirements, 23 January 2026. A separate TEC standard, TEC 33010:2025, sets generic technical and compliance requirements for IoT gateways in telecom networks, according to a summary by compliance firm Aleph India (Aleph India).
Before you buy, ask for the gateway's TEC certificate and check it was issued against the current version.
How do you size an IoT gateway?
| Factor | What to work out | Why it matters |
|---|---|---|
| Device count | Number of PLCs, meters, drives, sensors | Driver and licence limits; CPU load |
| Tags per device | Registers or variables you'll read | Total tags often decide the model |
| Polling rate | Seconds between reads per tag | RS-485 links saturate quickly at fast rates |
| Serial ports | Separate RS-485 lines needed | Split long or busy lines |
| Local storage | Hours or days of buffer needed | Covers network outages without data loss |
| Edge apps | Containers, scripts, analytics | Needs more RAM and CPU |
| Environment | Temperature, dust, DIN rail, power supply | Plant panels are hot; check rated range |
| Connectivity | Ethernet, 4G or 5G, Wi-Fi | Backup link for remote sites |
A simple sum helps: total tags divided by polling interval gives reads per second. Compare that with what the supplier says the gateway and each serial line can handle. Leave headroom of 30 to 50% for growth, as a rule of thumb.
For gateway hardware, see our edge computing and IoT gateway products and controllers and integration products.
Common mistakes
- One gateway for everything. A single box polling hundreds of devices on one serial line gives stale data. Split by area or line.
- No buffer. Cloud links drop. Without local storage, you lose the data you most need, during the outage.
- Hard-coded register maps. Keep tag lists in a managed file or template, so replacing a meter doesn't break dashboards.
- No owner. IT thinks the gateway belongs to the plant; the plant thinks it belongs to IT. Name an owner for patches and passwords.
Questions to ask an IoT gateway supplier
- Which protocol drivers are included, and which cost extra?
- How many tags and devices can it poll at our polling rate? Show test results.
- How much local buffer is there, and what happens when it fills?
- Does it support OPC UA security, MQTT over TLS and certificate management?
- Which ISA/IEC 62443 requirements does the product meet, and is that independently assessed?
- Do you hold a TEC certificate against the revised essential requirements for IoT gateways?
- How are firmware updates delivered and for how many years?
FAQs
What is an IoT gateway? A device that connects field equipment to IT or cloud systems. It reads data in industrial protocols, converts and buffers it, and sends it securely onward.
What is the difference between Modbus, OPC UA and MQTT? Modbus is a simple field protocol with no built-in security. OPC UA is an industrial protocol with a rich data model and built-in security. MQTT is a lightweight publish-subscribe protocol used to move data from gateways to platforms.
Which MQTT QoS level should I use? QoS 0 for frequent readings where one loss is acceptable, QoS 1 when delivery matters and duplicates can be handled, and QoS 2 when a duplicate or loss would cause an error.
Do IoT gateways need TEC certification in India? IoT gateways are covered by TEC essential requirements, which were revised on 19 June 2026. Ask suppliers for a certificate against the current version.
How many devices can one gateway handle? It depends on tags, polling rate, serial lines and edge apps. Work out reads per second and check against tested limits, with headroom.
Planning plant connectivity or an OT data platform? Talk to our IT and OT team or see our enterprise networking solutions.
Sources
- Gazette of India, S.O. 3349(E), revised TEC essential requirements including IoT gateways, 19 Jun 2026: egazette.gov.in
- OASIS, MQTT Version 5.0, OASIS Standard, 7 Mar 2019: docs.oasis-open.org
- OPC Foundation, OPC Unified Architecture: opcfoundation.org
- ISA, ISA/IEC 62443 series of standards: isa.org
- Aleph India, TEC notification of new standard for IoT gateways: alephindia.in