Short answer: most server rooms still run racks under 10 kW, and precision air conditioning (CRAC or CRAH units) with hot or cold aisle containment cools them well. Denser rows move to in-row coolers or rear-door heat exchangers, and the densest AI and HPC racks to direct liquid cooling (cold plates or immersion). Whatever you choose, keep server inlets in ASHRAE's recommended 18 to 27°C band and raise chilled water temperatures to cut energy.
This guide covers the temperature limits, the main cooling options and where each fits, what rack densities look like today, how cooling affects PUE, and what to ask a vendor.
What temperature should a data centre run at?
ASHRAE's thermal guidelines are the reference most operators and IT makers use. The US Department of Energy's 2024 best practices guide reproduces the 2021 envelope for air-cooled IT equipment (US DOE FEMP, Best Practices Guide for Energy-Efficient Data Center Design, revised July 2024):
| Envelope | Server inlet dry-bulb temperature | Relative humidity |
|---|---|---|
| Recommended (all classes A1 to A4) | 18 to 27°C | 8% to 70% |
| Allowable, class A1 | 15 to 32°C | 8% to 80% |
| Allowable, class A2 | 10 to 35°C | 8% to 80% |
| Allowable, class A3 | 5 to 40°C | 8% to 85% |
| Allowable, class A4 | 5 to 45°C | 8% to 90% |
The DOE guide says facilities should be designed and run to target the recommended range. The allowable envelope shows what equipment makers have tested for function, not reliability. It also warns about going too far: server fans speed up as inlet temperature rises, and a 30% rise in fan speed from 25°C to about 33°C inlet more than doubles fan power. The sweet spot is the upper part of the recommended range, measured at the server inlet, not at the CRAC return.
The guide also says data centres often over-control humidity for no real benefit. Tight humidity bands are a legacy habit and can usually be relaxed.
How dense are server racks today?
Density decides the cooling method. Uptime Institute's 2025 global survey asked 710 operators for their most common (modal) rack density (Uptime Institute Global Data Center Survey 2025):
The average modal density was almost 9 kW, up from 8.3 kW in 2024. Without the few very dense sites it was 7.5 kW. More than 80% of operators said they have no racks above 30 kW at all, and about one in eight had some racks in the 30 to 59 kW range. Uptime notes that a richly configured mainstream server can now draw close to 1 kW, so it doesn't take many to pass 10 kW in a rack. AI training racks are the outliers, concentrated in a few sites.
For most Indian enterprise server rooms, that means air cooling done well is still the answer. Plan the room so you can add higher-density cooling for a few AI or GPU racks later.
What are the main data centre cooling options?
| Option | How it works | Where it fits | Watch out for |
|---|---|---|---|
| Comfort split ACs | Room air conditioners blowing into the room | Small comms rooms only | Not built for 24x7 sensible load; poor humidity and airflow control |
| Precision AC (DX CRAC) | Packaged unit with its own compressor, perimeter or under-floor supply | Small and mid server rooms | Each unit needs an outdoor condenser; efficiency drops in Indian summers |
| Chilled water CRAH | Air handler with a chilled water coil, served by a central chiller plant | Mid to large data centres | Needs a chiller plant and piping; leak detection under the floor |
| In-row coolers | Cooling units placed between racks, pulling hot aisle air | Higher-density rows, containment pods | Takes rack space; needs chilled water or refrigerant to the row |
| Rear-door heat exchangers | A water coil in the rack's back door; passive or with fans | Retrofitting dense racks in an air-cooled room | Water at the rack; door weight and service access |
| Direct liquid cooling: cold plates | Liquid runs through plates on CPUs and GPUs via a coolant distribution unit (CDU) | AI and HPC racks | New piping, CDUs, server compatibility, maintenance skills |
| Direct liquid cooling: immersion | Servers sit in a tank of non-conductive fluid, single or two-phase | Very high densities, special builds | Fluid handling, floor loading, vendor support for immersed servers |
The DOE guide describes rear-door, in-row and overhead coolers as close-coupled air-to-liquid systems, and cold plates and immersion as direct liquid cooling. It says liquid cooling can serve higher heat densities and be much more efficient than air, because water carries heat far better.
How does cooling affect PUE?
Cooling makes up a large share of non-IT overhead, which is why PUE tracks cooling design so closely. Uptime's 2025 survey put the global weighted average PUE at 1.54. Our data centre BMS and PUE guide explains how to measure it.
The DOE guide lists the measures that matter most:
- Aisle containment. Separate hot and cold air so the cooling units see warmer return air and fans can slow down.
- Raise supply air and chilled water temperatures as high as possible while meeting the cooling load. Higher chilled water temperature improves chiller efficiency and adds economiser hours.
- Variable speed fans on CRAH units, and make all units work to the same setpoints so they don't fight each other.
- Economisers. A water-side economiser can cut or stop compressor use when outdoor conditions allow. In much of India these hours are limited, so model them for your city before counting on them.
- Size for part load. Data centres often run well below design load for years. Pick equipment that stays efficient at low load.
Our chiller plant optimisation guide covers the plant side in more detail.
What should Indian data centres plan for?
India's heat and humidity raise the cooling load and cut free-cooling hours. The Energy Conservation and Sustainable Building Code 2024 treats computer room air conditioning as its own category, where heat removal from equipment takes priority over comfort, and it lists data centres among the loads to be sub-metered in business buildings (ECSBC 2024, BEE). Three things help:
- Measure at the rack inlet. A 2016 CII and Lawrence Berkeley National Laboratory report for India recommended rack inlet temperature monitoring at the top of every fifth rack in the cold aisle (CII-LBNL, Accelerating Energy Efficiency in Indian Data Centers, Dec 2016). Control to that, not to return air.
- Contain first, then add capacity. Blanking panels, sealed cable cut-outs and containment often free up enough cooling to avoid buying another unit.
- Design a liquid-ready zone. Chilled water taps, space for a CDU and floor strength for a few dense racks cost little at design stage and a lot later.
For the market and policy picture, read our data centres in India 2026 post. For the wider infrastructure, see our data centre infrastructure solutions.
Questions to ask a data centre cooling vendor
- What rack density (kW per rack) is your design good for, and what's the plan for a few racks at 30 kW or more?
- What server inlet temperature will you design to, and where will it be measured?
- What's the cooling system's energy use at 25%, 50% and 100% of IT load?
- How do the cooling units share load and avoid fighting each other on humidity?
- What containment do you propose, and what does it do to fan power?
- For chilled water or liquid cooling: what leak detection and isolation valves are included?
- How many economiser hours do you expect in our city, and from which weather data?
- What N+1 redundancy do you provide, and what happens on a unit failure at full load?
FAQs
What is the ideal temperature for a server room? ASHRAE recommends 18 to 27°C at the server inlet, with relative humidity between 8% and 70%. Measure at the front of the racks.
Is a normal split AC enough for a server room? Only for a very small comms room. Precision AC is built for constant 24x7 sensible heat and better airflow and humidity control.
When do you need in-row cooling? When some racks run hotter than room cooling can handle evenly, or when you want a contained pod for a dense row. Ask the vendor for the kW per rack each option is rated for.
Is liquid cooling needed for AI servers? Often, for dense GPU racks. Uptime's 2025 survey found that more than 80% of operators still have no racks above 30 kW, so most sites can start with a small liquid-cooled zone.
Does raising temperature save energy? Yes, up to a point. Warmer supply air and chilled water improve chiller efficiency and economiser hours. Above the recommended range, server fans speed up and eat the savings.
Planning cooling for a server room or data centre? Talk to our IT infrastructure team.
Sources
- US Department of Energy, Federal Energy Management Program, Best Practices Guide for Energy-Efficient Data Center Design, revised July 2024 (includes the 2021 ASHRAE thermal envelope): PDF
- Uptime Institute, Global Data Center Survey 2025, Keynote Report 180, July 2025: PDF
- Confederation of Indian Industry and Lawrence Berkeley National Laboratory, Accelerating Energy Efficiency in Indian Data Centers, Phase II report, Dec 2016: PDF
- Bureau of Energy Efficiency, Energy Conservation and Sustainable Building Code 2024 (computer room air conditioning definition; data centre sub-metering): PDF